Features of the 9500 process controller
-
Full PID auto tuning
process controller
-
4-20mA input and output
-
Total of 3 outputs, from
4-20mA, SSR drive, relay
-
Input options:
4-20mA
Thermocouple
2 or 3 wire PT100
0-50mV, 0-5, 0-10V
-
Alarms with 5 options
-
PID heat-cool operation
-
Ramp & soak operation
-
Sleeve mounting for easy
maintenance
-
IP66 protection from
front panel
-
CE, UL & CSA approvals
-
3-year warranty
-
Charting and logging
software option
-
RS232/485 Modbus option
|
|

 |
Features of the 9500P (programmer)
-
Up to 31 programs
(profiles)
-
Up to 126 segments
-
Unlimited use of event
outputs via the 2nd and 3rd outputs
-
Copy/paste/edit/delete
functions to simplify program building
-
Call another program as a
sub-program segment
-
Up to 999 program loop
cycles, or continuous loop cycling
-
Hold back function to
ensure the next segment is not started until the last segment reaches
set-point
-
3 power fail recovery
options, (hold, continue or reset)
-
Front Panel Interrogation
of the program position
-
Memory usage indication
during programming
-
Front panel 'release from
hold' function to run the program.

|
|
9500 process controller |
|
1/16th DIN 48 x 48mm |
|
Set-point and process value shown. |
|
Options:
|
Inputs: |
sensor,
thermocouple, 0-5, 0-10, 4-20mA |
|
Outputs: |
(third is always
relay)
Outputs 1 & 2 a combination from:
SSR driver, relay, 4-20mA, 0-5V, 0-10V |
|
Communications: |
RS232, RS485 with
MODBUS RTU protocol |
|
|

The 9500 is
sleeve mounted allowing the
fitting of comms boards for networking |
|
Specification -
9500
|
Thermocouple types: |
|
9 types: |
|
B,E,J,K,L,N,R,S,T |
|
Standards: |
|
IPTS/68/ DIN 43710 |
|
CJC rejection: |
|
20:1 (0.05†/†C)
typical |
|
External resistance: |
|
100 ohms maximum |
|
Resistance
thermometers: |
|
RTD/PT100: |
|
2 & 3 wire |
|
Standards: |
|
DIN43760
(-200/400†C) |
|
Linear process
inputs: |
|
Options: |
|
0 to 50mV +/-0.1% |
|
|
|
4-20mA +/-0.1% |
|
|
|
0-5V +/-0.1% |
|
|
|
0-10V +/-0.1% |
|
Applicable to all
inputs (SM = sensor maximum) |
|
Calibration
accuracy: |
|
+/- 0.25% SM +/-1†C |
|
Sampling frequency: |
|
input 10Hz, CJC 2
sec. |
|
Common mode
rejection: |
|
Negligible effect up
to 140db, 240V, 50-60Hz |
|
Series mode
rejection: |
|
60db, 50-60Hz
|
|
Temperature
coefficient: |
|
50ppm/†C SM typical |
|
Reference
conditions: |
|
22†C +/- 2†C, rated
voltage after 15 minutes settling time. |
|
Output devices
(check configuration) |
|
SSd1 and SSd2 |
|
solid state relay
driver: to switch a remote SSR 6VDC (nominal) 20mA non-isolated |
|
Miniature power
relay: |
|
form A/SPST contacts
(AgCdO) |
|
rLY1, rLY2, rLT3: |
|
2A/250VAC resistive
load |
|
Analogue output: |
|
4-20mA 500 ohms max’
+/- 0.1% fs |
|
typical |
|
0-5Vdc 10mA (500
ohms min’) +/- 0.1% fs |
|
typical |
|
0-10Vdc 10mA (1K
ohms min’) +/- 0.1% fs |
|
General: |
|
Displays: |
|
Upper, 4 digits,
high brightness green LED 10.4mm (0.4") high. |
|
|
|
Lower, 4 digits,
high brightness orange LED 9mm (0.35") high. |
|
|
|
Digital range –199
to 9999 |
|
|
|
Hi-res mode –199 to
999.9 |
|
|
|
LED output
indicators – |
|
|
|
flashing SP1 square,
green; SP2/SP3 round, red. |
|
Keypad: |
|
3 elastomeric
buttons. |
|
Power Supply: |
|
100-240V AC, 50-60
Hz , (typ' 5.0 VA) |
|
Environmental: |
|
Humidity: |
|
Max’ 80% |
|
Altitude: |
|
up to 2000M |
|
Installation: |
|
categories II and
III |
|
Pollution: |
|
Degree II |
|
Protection: |
|
NEMA 4X, IP66 |
|
EMC emission: |
|
EN50081-1 FCC rules
15 sub-part J class A |
|
EMC immunity: |
|
EN50082-2 |
|
Ambient temperature: |
|
0-50†C (32-130†F) |
|
Mouldings: |
|
flame retardent
polycarbonate |
|
Weight: |
|
180g (6.4 oz) |
|
Dimensions: |
|
Front fascia: |
|
51.0 x 51.0mm (2.0"
x 2.0") (includes gasket) |
|
Sleeve length: |
|
106.7mm (4.2") (with
gasket fitted) |
|
Instrument body: |
|
44.8 x 44.8mm (1.76"
x 1.76") |
|
Overall length:
|
|
116.2mm (4.57") |
|